{"id":2005,"date":"2017-05-17T08:41:57","date_gmt":"2017-05-17T12:41:57","guid":{"rendered":"https:\/\/labeauairsol.ca\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/"},"modified":"2023-10-05T15:51:13","modified_gmt":"2023-10-05T19:51:13","slug":"corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower","status":"publish","type":"post","link":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/","title":{"rendered":"Corrective measures following the detection of legionella in a cooling tower"},"content":{"rendered":"<p><strong>Here is an extract from the article published in Climapresse (CETAF). To read the full article, <a href=\"http:\/\/cetaf.qc.ca\/nouvelles-et-evenements\/les-mesures-correctives-a-la-suite-de-la-detection-de-legionella-dans-une-tour-de-refroidissement\/\">click here<\/a>.<\/strong><\/p>\n<p><strong>To comply with the provisions of the regulation on water-cooled cooling tower installations, the owners of Quebec&#8217;s 1,700 or so cooling towers have had to meet several requirements concerning their facilities since 2014<a href=\"http:\/\/www2.publicationsduquebec.gouv.qc.ca\/dynamicSearch\/telecharge.php?type=1&amp;file=61543.pdf\">(Decree 454-2014<\/a>).<\/strong><\/p>\n<p>These new provisions were introduced following the outbreak of <a href=\"http:\/\/www.lapresse.ca\/le-soleil\/actualites\/sante\/201307\/17\/01-4671785-legionellose-a-quebec-un-an-apres-le-risque-persiste.php\">Legionnaires&#8217; disease in Quebec City in 2012<\/a>. The outbreak resulted in 181 reported cases, including 14 fatalities. After several weeks of investigation, a link was established with a cooling tower in the Saint-Roch district. The authorities&#8217; inability to identify the source of the outbreak was largely due to a lack of information about the cooling tower fleet. And let&#8217;s not forget the lack of control surrounding their management.<\/p>\n<p>Since the regulation came into force, towers must be registered with the R\u00e9gie du b\u00e2timent du Qu\u00e9bec within 30 days of commissioning, and again on March<sup>1 of<\/sup> each year. The owner must also have a maintenance program drawn up by a professional. This program must contain the measures to be applied in order to limit the development of <em>Legionella<\/em> bacteria as far as possible.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Here is an extract from the article published in Climapresse (CETAF). To read the full article, click here. To comply with the provisions of the regulation on water-cooled cooling tower installations, the owners of Quebec&#8217;s 1,700 or so cooling towers have had to meet several requirements concerning their facilities since 2014(Decree 454-2014). These new provisions were introduced following the outbreak of Legionnaires&#8217; disease in Quebec City in 2012. The outbreak resulted in 181 reported cases, including 14 fatalities. After several weeks of investigation, a link was established with a cooling tower in the Saint-Roch district. The authorities&#8217; inability to identify the source of the outbreak was largely due to a lack of information about the cooling tower fleet. And let&#8217;s not forget the lack of control surrounding their management. Since the regulation came into force, towers must be registered with the R\u00e9gie du b\u00e2timent du Qu\u00e9bec within 30 days of commissioning, and again on March1 of each year. The owner must also have a maintenance program drawn up by a professional. This program must contain the measures to be applied in order to limit the development of Legionella bacteria as far as possible.<\/p>\n","protected":false},"author":4,"featured_media":1810,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"_eb_attr":"","_uag_custom_page_level_css":"","footnotes":""},"categories":[1],"tags":[],"class_list":["post-2005","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-non-classifiee"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.4 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Corrective measures following the detection of legionella in a cooling tower - Lab&#039;eau-air-sol<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Corrective measures following the detection of legionella in a cooling tower - Lab&#039;eau-air-sol\" \/>\n<meta property=\"og:description\" content=\"Here is an extract from the article published in Climapresse (CETAF). To read the full article, click here. To comply with the provisions of the regulation on water-cooled cooling tower installations, the owners of Quebec&#8217;s 1,700 or so cooling towers have had to meet several requirements concerning their facilities since 2014(Decree 454-2014). These new provisions were introduced following the outbreak of Legionnaires&#8217; disease in Quebec City in 2012. The outbreak resulted in 181 reported cases, including 14 fatalities. After several weeks of investigation, a link was established with a cooling tower in the Saint-Roch district. The authorities&#8217; inability to identify the source of the outbreak was largely due to a lack of information about the cooling tower fleet. And let&#8217;s not forget the lack of control surrounding their management. Since the regulation came into force, towers must be registered with the R\u00e9gie du b\u00e2timent du Qu\u00e9bec within 30 days of commissioning, and again on March1 of each year. The owner must also have a maintenance program drawn up by a professional. This program must contain the measures to be applied in order to limit the development of Legionella bacteria as far as possible.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/\" \/>\n<meta property=\"og:site_name\" content=\"Lab&#039;eau-air-sol\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/labeauairsol\/\" \/>\n<meta property=\"article:published_time\" content=\"2017-05-17T12:41:57+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2023-10-05T19:51:13+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"960\" \/>\n\t<meta property=\"og:image:height\" content=\"640\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"Labeauairsol\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Labeauairsol\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"1 minute\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/\"},\"author\":{\"name\":\"Labeauairsol\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#\\\/schema\\\/person\\\/bb2f43da3405ac6e2fe9e689c0b2644b\"},\"headline\":\"Corrective measures following the detection of legionella in a cooling tower\",\"datePublished\":\"2017-05-17T12:41:57+00:00\",\"dateModified\":\"2023-10-05T19:51:13+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/\"},\"wordCount\":202,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#organization\"},\"image\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/labeauairsol.ca\\\/wp-content\\\/uploads\\\/2017\\\/01\\\/562130_10151756584015486_1029729891_n.jpg\",\"articleSection\":[\"Non classifi\u00e9(e)\"],\"inLanguage\":\"en-US\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/\",\"url\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/\",\"name\":\"Corrective measures following the detection of legionella in a cooling tower - Lab&#039;eau-air-sol\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/labeauairsol.ca\\\/wp-content\\\/uploads\\\/2017\\\/01\\\/562130_10151756584015486_1029729891_n.jpg\",\"datePublished\":\"2017-05-17T12:41:57+00:00\",\"dateModified\":\"2023-10-05T19:51:13+00:00\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/#primaryimage\",\"url\":\"https:\\\/\\\/labeauairsol.ca\\\/wp-content\\\/uploads\\\/2017\\\/01\\\/562130_10151756584015486_1029729891_n.jpg\",\"contentUrl\":\"https:\\\/\\\/labeauairsol.ca\\\/wp-content\\\/uploads\\\/2017\\\/01\\\/562130_10151756584015486_1029729891_n.jpg\",\"width\":960,\"height\":640},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Accueil\",\"item\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Corrective measures following the detection of legionella in a cooling tower\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#website\",\"url\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/\",\"name\":\"Lab\u2019eau-air-sol\",\"description\":\"La science au service de votre environnement\",\"publisher\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#organization\",\"name\":\"Lab'eau-air-sol\",\"url\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/labeauairsol.ca\\\/wp-content\\\/uploads\\\/2018\\\/09\\\/logo-lab-eau-air-sol.png\",\"contentUrl\":\"https:\\\/\\\/labeauairsol.ca\\\/wp-content\\\/uploads\\\/2018\\\/09\\\/logo-lab-eau-air-sol.png\",\"width\":134,\"height\":133,\"caption\":\"Lab'eau-air-sol\"},\"image\":{\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#\\\/schema\\\/logo\\\/image\\\/\"},\"sameAs\":[\"https:\\\/\\\/www.facebook.com\\\/labeauairsol\\\/\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/#\\\/schema\\\/person\\\/bb2f43da3405ac6e2fe9e689c0b2644b\",\"name\":\"Labeauairsol\",\"url\":\"https:\\\/\\\/labeauairsol.ca\\\/en\\\/author\\\/labeauairsol\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Corrective measures following the detection of legionella in a cooling tower - Lab&#039;eau-air-sol","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/","og_locale":"en_US","og_type":"article","og_title":"Corrective measures following the detection of legionella in a cooling tower - Lab&#039;eau-air-sol","og_description":"Here is an extract from the article published in Climapresse (CETAF). To read the full article, click here. To comply with the provisions of the regulation on water-cooled cooling tower installations, the owners of Quebec&#8217;s 1,700 or so cooling towers have had to meet several requirements concerning their facilities since 2014(Decree 454-2014). These new provisions were introduced following the outbreak of Legionnaires&#8217; disease in Quebec City in 2012. The outbreak resulted in 181 reported cases, including 14 fatalities. After several weeks of investigation, a link was established with a cooling tower in the Saint-Roch district. The authorities&#8217; inability to identify the source of the outbreak was largely due to a lack of information about the cooling tower fleet. And let&#8217;s not forget the lack of control surrounding their management. Since the regulation came into force, towers must be registered with the R\u00e9gie du b\u00e2timent du Qu\u00e9bec within 30 days of commissioning, and again on March1 of each year. The owner must also have a maintenance program drawn up by a professional. This program must contain the measures to be applied in order to limit the development of Legionella bacteria as far as possible.","og_url":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/","og_site_name":"Lab&#039;eau-air-sol","article_publisher":"https:\/\/www.facebook.com\/labeauairsol\/","article_published_time":"2017-05-17T12:41:57+00:00","article_modified_time":"2023-10-05T19:51:13+00:00","og_image":[{"width":960,"height":640,"url":"https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg","type":"image\/jpeg"}],"author":"Labeauairsol","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Labeauairsol","Est. reading time":"1 minute"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/#article","isPartOf":{"@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/"},"author":{"name":"Labeauairsol","@id":"https:\/\/labeauairsol.ca\/en\/#\/schema\/person\/bb2f43da3405ac6e2fe9e689c0b2644b"},"headline":"Corrective measures following the detection of legionella in a cooling tower","datePublished":"2017-05-17T12:41:57+00:00","dateModified":"2023-10-05T19:51:13+00:00","mainEntityOfPage":{"@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/"},"wordCount":202,"commentCount":0,"publisher":{"@id":"https:\/\/labeauairsol.ca\/en\/#organization"},"image":{"@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/#primaryimage"},"thumbnailUrl":"https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg","articleSection":["Non classifi\u00e9(e)"],"inLanguage":"en-US"},{"@type":"WebPage","@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/","url":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/","name":"Corrective measures following the detection of legionella in a cooling tower - Lab&#039;eau-air-sol","isPartOf":{"@id":"https:\/\/labeauairsol.ca\/en\/#website"},"primaryImageOfPage":{"@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/#primaryimage"},"image":{"@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/#primaryimage"},"thumbnailUrl":"https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg","datePublished":"2017-05-17T12:41:57+00:00","dateModified":"2023-10-05T19:51:13+00:00","breadcrumb":{"@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/#primaryimage","url":"https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg","contentUrl":"https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg","width":960,"height":640},{"@type":"BreadcrumbList","@id":"https:\/\/labeauairsol.ca\/en\/corrective-measures-following-the-detection-of-legionella-in-a-cooling-tower\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Accueil","item":"https:\/\/labeauairsol.ca\/en\/"},{"@type":"ListItem","position":2,"name":"Corrective measures following the detection of legionella in a cooling tower"}]},{"@type":"WebSite","@id":"https:\/\/labeauairsol.ca\/en\/#website","url":"https:\/\/labeauairsol.ca\/en\/","name":"Lab\u2019eau-air-sol","description":"La science au service de votre environnement","publisher":{"@id":"https:\/\/labeauairsol.ca\/en\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/labeauairsol.ca\/en\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/labeauairsol.ca\/en\/#organization","name":"Lab'eau-air-sol","url":"https:\/\/labeauairsol.ca\/en\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/labeauairsol.ca\/en\/#\/schema\/logo\/image\/","url":"https:\/\/labeauairsol.ca\/wp-content\/uploads\/2018\/09\/logo-lab-eau-air-sol.png","contentUrl":"https:\/\/labeauairsol.ca\/wp-content\/uploads\/2018\/09\/logo-lab-eau-air-sol.png","width":134,"height":133,"caption":"Lab'eau-air-sol"},"image":{"@id":"https:\/\/labeauairsol.ca\/en\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/www.facebook.com\/labeauairsol\/"]},{"@type":"Person","@id":"https:\/\/labeauairsol.ca\/en\/#\/schema\/person\/bb2f43da3405ac6e2fe9e689c0b2644b","name":"Labeauairsol","url":"https:\/\/labeauairsol.ca\/en\/author\/labeauairsol\/"}]}},"uagb_featured_image_src":{"full":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",960,640,false],"thumbnail":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n-150x150.jpg",150,150,true],"medium":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n-300x200.jpg",300,200,true],"medium_large":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n-768x512.jpg",768,512,true],"large":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",960,640,false],"1536x1536":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",960,640,false],"2048x2048":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",960,640,false],"featured-small":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n-640x200.jpg",640,200,true],"featured-medium":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n-960x400.jpg",960,400,true],"featured-large":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n-960x400.jpg",960,400,true],"featured-xlarge":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n-960x400.jpg",960,400,true],"fp-small":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n-640x427.jpg",640,427,true],"fp-medium":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",960,640,false],"fp-large":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",960,640,false],"fp-xlarge":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",960,640,false],"menu-24x24":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",24,16,false],"menu-36x36":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",36,24,false],"menu-48x48":["https:\/\/labeauairsol.ca\/wp-content\/uploads\/2017\/01\/562130_10151756584015486_1029729891_n.jpg",48,32,false]},"uagb_author_info":{"display_name":"Labeauairsol","author_link":"https:\/\/labeauairsol.ca\/en\/author\/labeauairsol\/"},"uagb_comment_info":0,"uagb_excerpt":"Here is an extract from the article published in Climapresse (CETAF). To read the full article, click here. To comply with the provisions of the regulation on water-cooled cooling tower installations, the owners of Quebec&#8217;s 1,700 or so cooling towers have had to meet several requirements concerning their facilities since 2014(Decree 454-2014). These new provisions&hellip;","_links":{"self":[{"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/posts\/2005","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/comments?post=2005"}],"version-history":[{"count":0,"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/posts\/2005\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/media\/1810"}],"wp:attachment":[{"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/media?parent=2005"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/categories?post=2005"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/labeauairsol.ca\/en\/wp-json\/wp\/v2\/tags?post=2005"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}